6ES7 193-4JA00-0AA0
Siemens Main Menu › SIMATIC S7 › ET 200 Modules
Siemens 6ES7 193-4JA00-0AA0 — ET 200S Terminating Module
6ES7 193-4JA00-0AA0 is the terminating module for an ET 200S station, part of the Siemens ET 200 family. Siemens documentation also calls it a Termination Module. It completes the station at its right-hand end and serves the backplane bus termination function. It is more than a plastic end cover.
Within the ET 200 system architecture, electronic modules, wiring bases and termination components have different roles. This part completes the row of ET 200 terminal blocks. It does not serve the same purpose as the connection modules and wiring bases carrying field wiring.
Function and common misunderstandings
The Siemens system manual states that ET 200S is not ready for operation without its terminating module. This station component does not replace the terminating resistor on a PROFIBUS cable. PROFIBUS and PROFINET interface modules handle network communication; 4JA00 terminates the station's own module assembly.
Product type: ET 200S termination accessory. Order number: 6ES7193-4JA00-0AA0. The Siemens data sheet lists 30 mm width, 106 mm height, 7.5 mm depth and an approximate weight of 50 g. Use the installation drawing when planning cabinet space rather than relying on these product dimensions alone.
Five checks before selection or maintenance
1. Correct system: Confirm that the required part is for ET 200S. Do not substitute an ET 200SP or ET 200iSP termination component simply because it belongs to the ET 200 family.
2. End position: Check that the terminating module is present after the final terminal. If modules have been added, it must occupy the new right-hand end of the station.
3. Physical condition: Inspect the housing, locking features and connection surfaces. A cracked, broken or distorted part should not be accepted merely because it appears to fit.
4. Module assembly: Check that the digital input modules, analog input modules and digital output modules have been fully seated after maintenance. These category links do not imply that every listed product is compatible with ET 200S.
5. Power and diagnostics: If the station does not start, do not focus only on the terminating module. Inspect the ET 200 power supply modules, missing electronic modules and backplane connections. Where the station is controlled by a Siemens S7 PLC system, include the controller's diagnostic records in the investigation.
Installation and return to service
For planned work, place the machine in a safe state and isolate station power. Fit the terminating module to the DIN rail on the right of the final terminal module, then slide it left until it locks into place. Check alignment rather than forcing the parts together.
Important maintenance detail: If the terminating module has been removed and refitted with power applied, or the backplane bus has been interrupted and restored during operation, Siemens requires the complete ET 200S supply to be switched off and on again to establish a defined station state. Prevent unexpected machine movement before carrying out this restart.
Editor's Note
This small component is easy to overlook when purchasing a used or dismantled ET 200S station. Check the delivery photographs to confirm that the terminating module is present and intact. If the station stops working after maintenance, inspecting the end module and terminal joints is a sensible step before replacing an expensive interface module. However, not every communication fault is caused by the terminator; use the diagnostic instructions for the installed IM module.
PDF manuals and technical documents: Visit Siemens ET 200 user manuals and PDF documents for ET 200S documentation. In system manual A5E00515771-06, installation and removal appear on pages 66–67, and the order number is listed on page 137.
Related Topics
Terminal Blocks · Connection Modules · Communication Interfaces
Otomasyon AVM
Siemens Main Menu · SIMATIC S7 · ET 200 Modules · ET 200 PDF Manuals · PLC and HMI