6ES7 193-4CA50-0AA0

6ES7 193-4CA50-0AA0 – Siemens ET 200S TM-E15C26-A1 terminal module

6ES7 193-4CA50-0AA0 is the TM-E15C26-A1 spring-terminal base for 15 mm electronic modules in Siemens ET 200S stations. It provides 2×6 connection points. Field wiring connects to the base, while the electronic module fitted above it processes the signals. Check the termination method, AUX1 requirements and electronic module’s terminal table together when selecting a base. See the ET 200 system overview for the station arrangement.

Eight numbered terminals and four AUX1 connections

Terminals 1–8 connect to the electronic module; their functions depend on the module fitted. A3, A4, A7 and A8 are all connected to the same AUX1 bus. These form twelve physical connection points, which do not define the number of input or output channels. The four A-labelled terminals do not provide four isolated potentials.

AUX1 passes continuously through the base and is accessible at these four terminals. The power buses from the power module also continue through it. Determine the potential assigned to AUX1 from the power supply module and station wiring diagram; the A marking alone does not establish a PE connection.

Differences from 4CA40, 4CA80 and 4CB30

6ES7 193-4CA40-0AA0 is the TM-E15S26-A1 screw-terminal version, while 6ES7 193-4CA80-0AA0 is the TM-E15N26-A1 Fast Connect version. Both have a 2×6 arrangement. 6ES7 193-4CB30-0AA0 is a TM-E15C24-01 spring-terminal base with 2×4 connections; AUX1 passes through it without accessible AUX1 terminals. Terminal count therefore matters where wires are connected to A3/A4/A7/A8. Compare other ET 200 terminal bases using their terminal markings and the electronic module’s requirements.

Electronic-module selection and terminal functions

The Siemens manuals for the 6ES7 134-4MB02-0AB0 current input and 6ES7 134-4JB01-0AB0 thermocouple input modules explicitly list 4CA50. The system manual’s assignment table also shows TM-E15C26-A1 for the module family containing the 6ES7 134-4NB50-0AB0 RTD High Feature. When selecting another analog input module, check the usable-terminal list for its exact order number.

For example, terminals 4 and 8 on the 4MB02 are L−, while A4 and A8 connect to AUX1. Keep the letter-prefixed and plain terminal numbers separate, and do not transfer this signal assignment directly to another electronic module. The A1 base also provides no internal thermocouple reference junction; select the compensation method using the relevant electronic module’s manual.

Dimensions and packaging

The data sheet specifies 15 × 157 × 43 mm, in width × height × depth order. One base weighs approximately 70 g, and the manufacturer’s packing unit contains five pieces. For a used offer, confirm from the listing whether the sale covers an individual base or a five-piece pack.

Mounting and spring-terminal wiring

The base mounts on a 35 mm rail. Siemens specifies a 3 mm screwdriver and an 11 mm stripping length for spring-terminal wiring. Open the spring with the screwdriver, fully insert the conductor, then withdraw the screwdriver to clamp it. Select conductor size and ferrules from the system manual’s wiring table. Switch off the relevant supply and load voltages before wiring.

During commissioning, compare wire markings with the channel definitions in the PLC project. See ET 200 PROFIBUS and PROFINET when reviewing the station’s network connection.

Editor’s Note: Request a clear photograph of the terminal face as well as the label when selecting a replacement. The A3, A4, A7 and A8 markings should be legible, with close views of the spring-terminal openings, side contacts and rail latch. Record 4 separately from A4, and 8 separately from A8. Do not transfer connections based on wire colour alone.

Manuals and PDF documents

Use the documents in the Siemens ET 200 manuals section. Section 1.7, pages 17–18 of the 04/2007 Terminal Modules manual explains the connection arrangement. In the 12/2004 system manual, pages 5-8 and 5-9 cover spring wiring and page 9-3 shows module assignments. Usable bases for the 4MB02 and 4JB01 appear on page 8 of their respective manuals.

Related topics

Browse industrial communication, PLC and HMI and Siemens S7-300 for other system components and applications.

Navigation

Siemens ET 200 | Siemens SIMATIC S7 | Siemens automation | OtomasyonAVM home