6ES7 193-1FL20-0XA0
Siemens 6ES7 193-1FL20-0XA0 – ET 200L 32-Channel Single-Tier Screw-Type Add-on Terminal
The Siemens 6ES7 193-1FL20-0XA0 is a 32-channel, single-tier add-on terminal with screw connections for SIMATIC ET 200L stations. Within the ET 200 range, it belongs to the wiring hardware used to organise field connections. When identifying a spare, the term add-on terminal matters: this component is supplied and selected separately from the electronic I/O block.
In an industrial automation system, the PLC program, field signals and physical wiring all have distinct roles. This part serves the wiring side. The installed electronic block determines the station’s I/O functions; fitting the add-on terminal does not create additional input or output addresses.
TB32L mounting and the common terminal row
This version is intended for the TB32L arrangement and fits into guides beneath the main terminal block. Siemens states that the terminals within each tier are internally jumpered; the single-tier drawing identifies the row as PE. Follow the markings and the station wiring diagram. Protective earthing and the control circuit’s M/0 V connection have different functions.
The 32-channel designation does not mean 32 isolated signal terminals. Connecting several independently monitored sensor outputs to a common row would join those signals together. The internal bridging arrangement determines which conductors may share that row. Counting the terminals is therefore only one part of identifying the correct component.
When checking digital input wiring, trace the supply, signal output and common connection of each inductive sensor against its own diagram. Also verify PNP/NPN and sinking/sourcing compatibility between the sensor and the input circuit. An add-on terminal does not convert one output type into another.
How the similar order numbers differ
1FL20 identifies the single-tier screw-type version. In the same 32-channel group, 1FL30 is the two-tier screw-type version, 1FL50 is single-tier spring-type, and 1FL60 is two-tier spring-type. Their complete order numbers are 6ES7193-1FL30-0XA0, 6ES7193-1FL50-0XA0 and 6ES7193-1FL60-0XA0. Check both the number of tiers and the connection method before treating a similar-looking part as a replacement.
For terminal block selection, identify the ET 200L subfamily and the existing TB32L assembly together. ET 200S terminal modules and ET 200SP BaseUnits use different arrangements. The TB32L main terminal block and this add-on are also separate components. Compare the label and mounting location so that the spare matches the part actually requiring replacement.
Installation and wiring checks
Safely isolate the relevant circuits and verify absence of voltage before work begins. Record the connections and make sure wire markers remain legible before disconnecting anything. Inspect the locating guides, latch and screw housings. A cracked body or damaged thread needs proper assessment; tightening a screw harder is not a remedy for mechanical damage.
Use the applicable connection instructions to select conductor size, end preparation and tightening torque. Do not clamp insulation inside the contact or leave excess bare conductor exposed. Arrange the cables and connectors so that they do not pull on the terminal assembly. The Siemens drawing gives a length of 191 mm for the TB32L single-tier add-on terminal. The product record lists a net weight of 0.162 kg. Packaging dimensions should not be used as installation dimensions.
Locating a fault during maintenance
If several signals disappear in the same area, inspect shared connections, the power supply and field wiring together. For a fault affecting one channel, compare the sensor output, cable termination and electronic input status. On the digital output side, load and wiring faults also need to be distinguished from a failed electronic block. These checks guide the investigation; a symptom alone does not prove that the terminal assembly is defective.
PROFIBUS communication settings belong to the station’s electronic block and control configuration. This passive terminal has no separate firmware installation or independent network address. After replacement, verify wire identification, shared connections and the machine’s expected I/O behaviour together.
Selecting a replacement part
The Siemens product record gives 1 October 2024 as the lifecycle end date, with PM500 status and no listed direct successor. For an existing machine, match the full order number, the single-tier screw connection arrangement and the physical condition of the replacement. The order number alone does not establish whether an individual unit is new, used or refurbished.
Editor’s note: The easy mistake is to assume that a similar-looking terminal performs the same job. Establish the ET 200 subfamily, tier count, connection method and internal bridging first. That is much quicker than tracing an entire set of wires after the wrong part has been fitted.
Manuals and PDF documents
Use the Siemens ET 200 user manuals and PDF documents page to access the documentation archive. The source manual for this component is ET 200L Distributed I/O Device, edition 10/2005, document EWA-4NEB 780600902-05. Supplementary terminals are covered in section 7.3, with order numbers in Appendix A.1. Check that the selected document covers ET 200L.
Related topics
ET 200 system structure · ET 200 connection modules · ET 200 additional modules and accessories · ET 200 power supply modules · ET 200 power distribution modules. These pages explain other roles and options within the range; compatibility still needs to be checked against the complete order number.
Navigation: Siemens automation · Siemens S7 PLC · SIMATIC S7 · Siemens ET 200.
Technical sources: Siemens Industry Mall, 6ES7193-1FL20-0XA0 product record; Siemens ET 200L Distributed I/O Device, 10/2005, sections 2.1, 7.3 and Appendix A.1.