6ES7 193-0CC10-0XA0
Siemens 6ES7 193-0CC10-0XA0 – ET 200B TB6/AC Terminal Block
Siemens 6ES7 193-0CC10-0XA0 is the TB6/AC terminal block for ET 200B within the SIMATIC ET 200 family. It provides three-tier screw terminals and a 235 mm width for 16-channel AC electronics blocks.
When selecting a replacement, check the terminal block reference together with the part number of the installed electronics block. Similar dimensions or terminal arrangements do not establish compatibility between different ET 200 terminal blocks.
Compatible electronics blocks
6ES7 131-0HF00-0XB0 / ET 200B-16DI-AC: 16 AC digital inputs.
6ES7 132-0HF00-0XB0 / ET 200B-16DO-AC: 16 AC digital outputs.
6ES7 132-0HH00-0XB0 / ET 200B-16RO-AC: 16 relay outputs. 6ES7 133-0HH00-0XB0 / ET 200B-8DI/8RO-AC: 8 AC inputs and 8 relay outputs.
For a useful replacement enquiry, include the complete electronics block reference, the cabinet wiring diagram and a description of the fault. An input circuit and a relay contact require different checks, so identifying the installed hardware is more helpful than describing the assembly only as an “ET 200 module.”
Supply voltage and field circuits
The AC electronics supply is rated 120/230 V AC, with an allowable range of 85–264 V AC. This supply rating must not be treated as the switching rating of every output contact.
Before connecting a contactor coil, indicator lamp or another load, compare its voltage, operating current and switching characteristics with the specifications of the actual electronics block. Review the cabinet’s power supply arrangement and trace external load circuits separately from the electronics supply. This makes it easier to determine whether a problem originates in the supply, the output stage or the field wiring.
PROFIBUS connection and station identification
The base carries a PROFIBUS-DP socket, station address selectors and a mechanical coding slide. Terminal assignments depend on the fitted electronics block.
When troubleshooting an automation system, compare the station address with the project configuration before replacing hardware. Check the PLC hardware configuration, field address and PROFIBUS connection together. Photographs of the address selectors and coding slide provide a useful record before removal.
Screw terminals and wiring checks
Siemens’ general wiring table specifies maximum supply and signal conductor sizes of 1.5 mm² with ferrules and 2.5 mm² without ferrules.
A maintenance inspection should cover more than screw tightness. Check that each conductor is seated correctly, that no loose strands remain exposed and that the surrounding insulation shows no cracking or heat damage. Field cables and connectors must suit the circuit voltage and installation conditions.
Review protective conductors and grounding against the cabinet drawings. Wire colour and physical proximity are not reliable substitutes for a terminal assignment diagram. Match the numbered connection points to the documentation for the installed electronics block before making changes.
Fuse selection and power isolation
TB6/AC has no STOP/RUN switch. Disconnect external power before removing the electronics block or replacing the fuse. The specified fuse is TR5-T 1 A / 250 V AC, order number 6ES7 193-0DC00-0XA0.
Do not use this fuse rating as a per-channel output current rating. If the fuse opens repeatedly, investigate the fault instead of fitting a higher current replacement. Account for separately supplied load circuits and verify the absence of voltage at the work location before starting maintenance.
Replacement selection and fault assessment
Provide the complete 6ES7 193-0CC10-0XA0 reference and separate photographs of the terminal block and electronics block labels. Report damaged terminals, cracked housing, deteriorated contact surfaces or visible heat marks alongside the electrical symptoms.
A single channel failing to operate and an entire station disappearing from the network are different symptoms. Recording measurements and observed behaviour helps narrow the investigation and avoid unnecessary replacement. When reviewing a quotation, confirm whether the electronics block, connection plugs and any accessories shown in photographs are included in the offered item.
Editor’s note: The most useful starting point is a clear record of both part numbers. Keeping the labels, wiring diagram and existing address settings together makes the replacement enquiry easier to assess and leaves a better maintenance record for the next technician.
Technical documentation and connection diagrams
Reference: Siemens ET 200B Distributed I/O Station, EWA 4NEB 812 6089-02c; sections 7.2.8 and 7.3.11–7.3.14. Start your document search from our Siemens ET 200 manuals and PDF documentation page.
Related information and product categories
For an introduction to the product family, visit About Siemens ET 200. You can also browse connection modules, additional modules, power supply modules and power distribution modules. These category links are browsing references; compatibility must be checked for each individual part.
Explore Siemens products: Siemens | Siemens S7 PLC | SIMATIC S7 | ET 200 products