6ES7 171-1AA01-0AA0
6ES7 171-1AA01-0AA0 – Siemens ZA 724 Central Interface
6ES7 171-1AA01-0AA0 is the ZA 724 central interface for the Siemens HS 724 heating controller. It communicates with the PLC as a PROFIBUS-DP slave and passes heating commands to the LA 724 power-output modules. This version supports communication rates of up to 12 Mbit/s.
System arrangement and capacity
Two 724 parallel buses serve up to 16 LA 724 modules in two groups of eight. With 24 channels per power module, the total capacity is 384 heater channels.
The Siemens sample application uses an S7-300 or S7-400 CPU with an integrated PROFIBUS-DP interface. Record the installed CPU model, station address and power-module sequence before replacing a component.
Supply and connections
The supply is 230 V AC, 50/60 Hz, with a permissible range of 187–264 V AC. Power consumption is 35 W typical and 46 W maximum.
Rotary switches set the PROFIBUS address from 00 to 99. The RS232 connection is used for firmware loading. Status indicators are a green Ready LED and a red Error LED. When investigating a fault, record the LED state alongside the diagnostic message reported by the PLC.
GSD file and version differences
The Siemens HS 724 software documentation specifies SIEM002B.GSD and the HSSYNC-1.EXE firmware loader for this model. The earlier 6ES7 171-1AA00-0AA0 version is limited to 1.5 Mbit/s and uses SI002BTD.GSD and HSSYNC.EXE.
Keep the existing hardware configuration and firmware details when selecting a spare. Match the GSD file and loading tool to the complete order number, and verify the installed firmware version from the actual device.
Related models and replacement checks
When comparing power outputs such as 6ES7 171-2AA00-0AA0, distinguish the central interface’s role from that of the output module. The later HS 724i system lists a ZA 724 with order number 6BK1700-2BA30-0AA0. Sharing the ZA 724 name does not establish direct interchangeability.
For a used unit, inspect the label, supply connections, bus sockets and signs of previous work. Ask how PLC communication and operation with connected power modules were verified, as well as whether the unit powers up.
Editor’s Note: Keep the PROFIBUS address, GSD file and project backup with the spare’s complete order number. During a machine stoppage, knowing the installed configuration can save as much time as locating the correct hardware. Confirm which connection plugs are included before placing an order.
Manuals and PDF documents
Use the Siemens ET 200 manuals section for documentation. Hardware details come from HS 724, 05/2001, Section 2.1; GSD and loader references come from S7 Sample Program for HS 724, V0.4, pages 8–10. The HS 724i model comparison uses Appendix A of its manual.
Related topics
Explore other heating-system components through controllers, temperature controllers and temperature sensors. For control hardware, see PLCs and modules, PLC and HMI and Siemens S7 PLC.
Browse other groups under ET 200 digital outputs, function and safety modules, special output modules and the special application product index. Verify suitability against each model’s own manual.