6ES7 158-0AD01-0XA0

6ES7 158-0AD01-0XA0 – Siemens SIMATIC DP DP/DP Coupler

6ES7 158-0AD01-0XA0 is a Siemens DP/DP coupler for exchanging data between two independent PROFIBUS-DP networks. It operates as a DP slave on each network, transferring one master system’s output data to the other system’s inputs. See PROFIBUS and PROFINET for more about these network types.

Data capacity and communication

The data exchange capacity is 244 input bytes and 244 output bytes. Up to 16 I/O areas can be configured, with a 128-byte consistency limit. The two sides can use different PROFIBUS addresses and transmission rates. The maximum supported rate is 12 Mbit/s.

Configuring both networks

Configure the coupler separately in each master project. Output areas on one side must match the length and sequence of the input areas on the other. For example, 16 output bytes from the first PLC are configured as 16 input bytes in the second PLC; apply the same arrangement in the reverse direction.

Assign each network side an address from 1 to 125. In an S7-300 project, check the CPU model, DP master interface and existing hardware configuration together. Back up both projects before replacing the unit.

Supply, connections and data validity

The nominal supply is 24 V DC, with a permissible range of 20.4–28.8 V DC. Two independent sources can provide a redundant supply; if one fails, the other maintains power. This redundancy applies to the coupler’s supply inputs. The two PROFIBUS networks are galvanically isolated.

With the DIA switch set to ON, the least significant bit of the first configured input byte is reserved for data validity. Siemens recommends reserving the entire first byte from normal user data. Check the existing program’s data layout alongside this setting.

Earlier version and related couplers

Siemens supports using this model to replace the earlier 6ES7 158-0AD00-0XA0. Check the existing configuration and diagnostic-data evaluation when replacing it.

6ES7 158-3AD00-0XA0 is a PN/PN coupler for two PROFINET networks. 6ES7 157-0AC83-0XA0 is the DP/PA FDC 157-0 model. Select the device for the protocols of the networks being connected, and browse other network interfaces for further options.

For a used unit, check the full order number, both 9-pin D-sub sockets and the switches. Ask how data exchange in both directions and the supply inputs used during testing were verified.

Editor’s Note: If one network side fails, the output values of the other side are retained. Evaluate data freshness through the PLC’s diagnostics and validity handling. Keep the diagnostic information and validity method with the project, and verify the application’s response when communication is lost and restored.

Manuals and PDF documents

Use the Siemens ET 200 manuals section for documentation. Configuration and diagnostics were checked against DP/DP Coupler, 02/2006, Sections 4 and 6, and electrical data against Appendix A. For network connections and coupler types, see PROFIBUS Networks, 04/2009, pages 89–90.

Related topics

Explore other system components under PLCs and modules, PLC and HMI, power supply modules, connection modules and terminal blocks.

Other product groups include digital input modules, digital output modules and the special application product index. Verify each component’s suitability using its own order number and manual.