6ES7 157-0AC00-0XA0
Siemens 6ES7 157-0AC00-0XA0 PROFIBUS DP/PA Coupler
Siemens 6ES7 157-0AC00-0XA0 is a non-intrinsically-safe DP/PA coupler used to connect PROFIBUS PA field instruments to a PROFIBUS DP network. It provides the communication interface between process instrumentation and the PLC system. Although it may appear in installations containing Siemens ET 200 stations, its purpose is bus coupling rather than providing conventional input or output channels.
Suitable field instruments
The module converts the DP-side RS-485 physical layer to the IEC 61158-2 transmission system used by PROFIBUS PA, with electrical isolation between the two sides. Typical applications involve pressure, temperature, level and flow instruments equipped with a PROFIBUS PA interface. When selecting a sensor, check its communication option as carefully as its measuring range.
A transmitter with a conventional 4–20 mA output or 0–10 V output is not automatically a PA device. It requires a suitable analog input solution. Checking the installed instrument’s full model and interface designation before ordering the coupler helps avoid unnecessary changes elsewhere in the system.
Communication rates and the DP/PA Link distinction
In standalone operation, the DP side runs at 45.45 kbit/s and the PA side at 31.25 kbit/s. The DP master and other relevant network components must support that DP rate. PROFIBUS and PROFINET are different communication systems; this module provides a DP/PA connection. The ET 200 communication overview provides additional background for network selection.
The coupler and IM 157 are separate devices. Combining the original 6ES7 157-0AA00-0XA0 IM 157 with DP/PA couplers creates a DP/PA Link. That arrangement supports an upstream DP rate of up to 12 Mbit/s and up to five couplers. The Link’s 12 Mbit/s capability must therefore not be quoted as the standalone DP speed of 6ES7 157-0AC00-0XA0.
Power supply and PA segment capacity
The coupler uses a 24 V DC supply and provides a maximum PA output current of 400 mA. This is the current budget for the segment, not the consumption allowance for each instrument. Device consumption, fault currents, cable resistance and the voltage available at the most distant instrument all affect the usable device count.
The PA bus supply must also be distinguished from the coupler’s 24 V DC input. When selecting the cabinet power supply, assess the coupler together with the other connected loads. A suitable DIN rail power supply does not remove the need for a separate PA segment calculation. Likewise, cable length should be checked against the actual installation rather than chosen from a single headline distance.
Connections, dimensions and installation
The DP interface uses a 9-pin Sub-D connector; PA wiring uses four screw terminals. The internal PA termination is selectable. The enclosure is rated IP20, with dimensions of 80 × 125 × 130 mm, stated as width, height and maximum installation depth. The module mounts horizontally on an S7-300 mounting rail, with 40 mm installation clearance above and below.
PA terminators must be positioned to suit the segment topology. Shield continuity, equipotential bonding and cable routing also influence communication quality. Reviewing potential electromagnetic interference sources is useful; adding an EMC filter alone will not correct faulty shielding or bus termination.
Configuration and maintenance
In standalone use, the coupler is transparent to communication and does not require its own station address or GSD configuration. The PA instruments are configured using their appropriate GSD files. Instrument parameters can be handled through compatible SIMATIC PDM software or a supported manufacturer tool. Initial troubleshooting should consider the DP rate, instrument addresses, power supply and termination together.
For a replacement, compare the complete order number, terminal condition and existing network arrangement. Similar-looking connection modules do not necessarily have matching electrical characteristics. When consulting the Siemens ET 200 manuals page, check that the selected document covers the original 0AC00 version.
Editor’s note: 6ES7 157-0AC00-0XA0 does not provide the intrinsically safe PA output of the Ex [i] version. Specifications belonging to 0AD00 or later 0ACxx models should not be transferred to this unit. Before arranging a replacement, record whether the installed coupler operates independently or through an IM 157.
Related topics
For other elements of distributed automation, see ET 200 power supply modules, power distribution modules and ET 200 additional modules. These pages provide general background rather than a list of directly compatible accessories.