6ES7 153-2BA02-0XB0
Siemens 6ES7 153-2BA02-0XB0 – ET 200M IM 153-2 High Feature PROFIBUS Interface Module
Siemens 6ES7 153-2BA02-0XB0 is an IM 153-2 High Feature interface module for SIMATIC ET 200M distributed I/O stations. It manages PROFIBUS DP communication between the station’s I/O modules and the central control system. Within the Siemens ET 200 range, this model enables compatible S7-300 modules to operate as distributed I/O. The control program runs in the main PLC, while the IM 153-2 transfers station data.
PROFIBUS Connection and Network Integration
The module uses a 9-pin Sub-D RS-485 interface for PROFIBUS DP communication at rates up to 12 Mbit/s. Its station address and hardware configuration identify it within the network. When checking an existing installation, cable shielding, termination and connector condition should be considered together. Our PROFIBUS and PROFINET guide explains the network technologies, while the ET 200 communication modules section covers related product groups.
Station Capacity and I/O Selection
The interface supports up to 12 compatible S7-300 I/O modules, with a maximum process data capacity of 244 input bytes and 244 output bytes. Both module count and data allocation need checking during selection. Analog values and additional status information contribute to the data requirement. Compatible 64-channel digital modules are also supported.
Digital input modules collect signals from sensors and photoelectric sensors. Digital output modules control electrically suitable loads or interposing relays. The selected I/O module determines the electrical characteristics of each channel.
High Feature Functions and Event Recording
Time stamping helps establish the sequence of digital events. Capacity reaches 128 digital signals per station and 32 per slot. With suitable input modules and clock synchronization, the specified accuracy is 1 ms with up to eight input modules, or 10 ms with up to twelve modules. This distinction matters when event records will be evaluated through an HMI or SCADA system.
Expanded support for HART auxiliary variables operates through compatible HART I/O modules. Related options can be reviewed under ET 200 special input modules and functional modules. The interface also supports isochronous operation when the DP master, I/O modules and project configuration meet the applicable requirements.
Redundancy and Module Replacement During Operation
A redundant station requires two compatible IM 153-2 interfaces, a suitable active BM IM/IM bus module and a supported control system configuration. Replacing I/O modules during operation also requires the appropriate rail and active bus modules. Inspecting the existing backplane arrangement is therefore an essential part of planning these functions. The choice of ET 200 connection modules affects how the station can be maintained.
Power Supply and Cabinet Installation
The rated supply is 24 V DC, with an operating range of 20.4–28.8 V DC. The backplane supply provides 5 V DC at up to 1.5 A; field load power must be calculated separately. Select the power supply, relevant ET 200 supply modules and fuses according to the complete station load.
The module has an IP20 protection rating and measures 40 × 125 × 117 mm. Permitted operating temperature is 0–60 °C for horizontal mounting and 0–40 °C for vertical mounting. Cabinet airflow, cable routing and grounding should be considered together when arranging the station.
Commissioning and Replacement Compatibility
Before commissioning, compare the physical module sequence and PROFIBUS address with the STEP 7 hardware configuration. Projects using GSD files require the correct device definition. During troubleshooting, review diagnostic information alongside the power supply and physical network connections. Keeping a project backup and clear records of the installed module labels makes subsequent replacements easier to assess.
Siemens identifies 6ES7153-2BA10-0XB0 as the successor. However, the 2BA10 cannot operate on BM 6ES7195-7HD00-0XA0. A replacement assessment should therefore cover the bus module, firmware, configured device and any redundant partner interface. Recording the complete order number helps purchasing and maintenance teams evaluate the same hardware.
Editor's Advice
When selecting a spare, record the bus module order number alongside the interface label. For redundant stations, include the second IM’s details. Where event recording is used, retain the clock synchronization settings as well. This gives the maintenance team a practical reference for checking compatibility before scheduling a replacement.
Technical Documents and Related Topics
Visit our Siemens ET 200 manuals and PDF documents section for technical documentation. Check that the document covers the IM 153-2BA02 version, particularly when comparing older hardware with a proposed replacement.
Related topics: About Siemens ET 200 · ET 200 additional modules · ET 200 terminal blocks