6ES7 153-2AA01-0XB0
6ES7 153-2AA01-0XB0 – Siemens ET 200M IM153-2 PROFIBUS Interface Module
6ES7 153-2AA01-0XB0 is an IM153-2 interface module for the ET 200M system within the Siemens ET 200 family. It connects S7-300 signal and function modules to a central controller over PROFIBUS DP. The module exchanges I/O data between the remote station and the PLC CPU that runs the control program; it does not execute a standalone user program.
Station role and module capacity
This order number supports up to 8 S7-300 signal or function modules after the interface. A station may use suitable SM 321 digital input, SM 322 digital output, analog I/O and function modules, according to the application. The eight-module limit does not imply support for every S7-300 module. Siemens explicitly excludes FM 356-4 in its compatibility listing; other specialised modules must also meet the requirements in their own documentation.
Supply, connections and commissioning
The module uses a 24 V DC supply and an electrical PROFIBUS interface based on RS-485. Review the station’s power supply and connection components together. During commissioning, compare the physical PROFIBUS address with the project, then check the module order, complete part numbers and I/O addresses against the existing STEP 7 hardware configuration. Measure the supply at the module terminals as well as at the power supply output.
Limits of the 2AA01 version
Siemens’ version comparison shows that 2AA01 does not support redundant IM operation, DPV1 mode, input time stamping or isochronous operation. Features available on later IM153-2 versions must not be assumed for this model. I/O module replacement during operation requires the appropriate active bus arrangement and configuration; it is not general permission to remove a module from an ordinary powered station.
A specific distinction when using CP 342-2
The Siemens CP 342-2 Product Information explicitly identifies 6ES7153-2AA01-0XB0 for extended AS-i operation using FC “ASI_3422” in ET 200M. When replacing the interface in an older AS-i station, check the CP version, FC function and CPU version together. The same document associates an intermittent 80C2 response during a data-record read with the CP being temporarily busy; this response alone does not establish an IM153-2 hardware fault.
Fault investigation and replacement selection
For a communication failure, a practical starting point is to check the supply, station address, PROFIBUS cable, shielding, bus termination and project configuration before replacing hardware. Assess the indicator LEDs together with the CPU’s diagnostic records. Record the full order number and hardware revision of the installed interface. If a different IM153-2 is proposed, verify compatibility with the existing I/O modules, bus base and project settings.
Editor’s Note: The decisive detail is the 2AA01 suffix on the label. This version is unsuitable where redundant interface operation is required. When sourcing a replacement, compare the complete label and hardware revision as well as the front view; a similar-looking module should not be assumed to provide the same functions.
User manuals and PDF documents
Use the Siemens ET 200 manuals and PDF documents page for installation, connection and version references. For this model, consult Appendix A.2, version compatibility, in ET 200M Operating Instructions, 12/2008, together with the ET 200M operating restrictions in CP 342-2 Product Information, 06/1998.
Related topics
For other station components, see ET 200 function modules, counter modules, positioning modules, terminal blocks and additional modules and accessories. The Siemens ET 200 overview explains the wider system family. These sections include products from different ET 200 architectures; mechanical and functional compatibility must be checked against the complete part number.