6ES7 153-1AA02-0XB0
6ES7 153-1AA02-0XB0 — Siemens IM153-1
Series: Siemens SIMATIC S7 / SIMATIC DP. Category: ET 200M PROFIBUS DP interface module.
6ES7 153-1AA02-0XB0 is an IM153-1 interface connecting an ET 200M station of S7-300 I/O modules to a PROFIBUS DP master. Field signals are handled by the adjacent modules; the interface transfers their data to the controller. It is not a CPU running a user program. Among PROFIBUS and PROFINET interfaces, this model uses electrical PROFIBUS DP / RS-485, with no PROFINET or integrated fiber-optic connection.
Station capacity and power supply
One interface supports up to 8 suitable S7-300 modules. This is a module limit, not a channel count; the installed modules determine the total I/O capacity. When selecting digital input and digital output modules, check that their exact order numbers are supported by the hardware catalog or GSD configuration in use.
The nominal supply is 24 V DC, with a permissible range of 20.4–28.8 V DC, connected to L+ and M. Size the power supply using the interface and module consumption separately from field-load currents. For power distribution calculations, do not transfer the newer 1AA03 version’s electrical ratings to this older unit; use its label and the applicable documentation revision.
PROFIBUS connection and commissioning
The network connection is a 9-pin female Sub-D socket. The maximum supported rate is 12 Mbit/s, and station addresses range from 1 to 125. The hardware address switches must match the address assigned in the project. Permissible cable length depends on the selected transmission rate and segment layout.
Enable termination at both ends of an RS-485 segment and leave it disabled at intermediate nodes. Where the connector’s termination is powered by the station, switching off an end station can also affect communication. Check the connection components, shielding and terminal arrangement before replacing the interface.
In STEP 7 hardware configuration, select the IM153-1 and the actual module sequence. With a third-party master, install the appropriate GSD file. First compare the physical station with the configured modules and addresses; matching the number of modules alone is insufficient.
Hardware revision and supported functions
This model supports SYNC and FREEZE. Direct data exchange is available from E07. The Siemens compatibility table lists no DPV1 or 64-byte extended diagnostics support for this order number; basic diagnostics are still available. Features of later IM153-1 versions should not be assumed from the family name.
E05 and later also have a specific restart behavior: with response monitoring disabled, if the master fails and restarts without resetting the DP slave, output values remain until new data arrives. Outputs therefore cannot be assumed to reset under every communication-loss condition. Check master-failure and restart behavior during commissioning.
Module replacement and related versions
Replacing I/O modules during operation requires suitable active bus modules and an enabled configuration. This does not apply to every installation using standard bus connectors. Disconnect the supply when replacing the IM153-1 interface itself. This model does not replace the dual-interface redundant arrangement provided by the IM153-2 family.
Siemens identifies 6ES7 153-1AA03-0XB0 as the successor. Before replacement, check the existing project, E-Stand and installed I/O together. For function modules, counter modules and positioning modules, a catalog entry alone does not establish compatibility: the operating mode supported with IM153-1 also matters. Suitability for safety modules and PROFIsafe requires a separate check.
Editor’s note: Do not select a replacement from the “IM153-1” marking alone. Read the full order number and E-Stand, and record the existing PROFIBUS address. Establish whether the fault affects one channel or the whole station. Restored communication is not a complete acceptance test: check how the outputs behave when the master stops and restarts.
PDF documentation and manuals
Read the ET 200M manual’s IM153-1 compatibility table, startup with response monitoring disabled and interface replacement sections together. Documentation is available through the Siemens ET 200 PDF and user manuals page.
Related topics
ET 200 system structure · Other network interfaces · Additional modules and accessories. Different ET 200 subfamilies may use different mechanical and electrical arrangements.