6ES7 151-3BA20-0AB0

Siemens 6ES7 151-3BA20-0AB0 ET 200S IM151-3 PN High Feature

The Siemens 6ES7 151-3BA20-0AB0 is an IM151-3 PN HIGH FEATURE interface module for ET 200S. It connects a remote I/O station to a PROFINET IO controller, passing input data to the PLC and returning output commands to the station. The PLC runs the control program; the IM151-3 handles the station’s network connection. Siemens also lists the part number as 6ES7151-3BA20-0AB0.

Network connections and station layout

An integrated two-port Ethernet switch provides two RJ45 connections, allowing the network cable to continue to the next device in a line topology. Communication runs at 100 Mbit/s. For an overview of the available network types, see ET 200 PROFIBUS and PROFINET.

The station supports up to 63 peripheral modules within a maximum station bus length of 2 metres. Module count is only part of the layout: power groups and their loads also need to suit the installed I/O. A station can combine the input, output and specialist modules needed by that part of the machine.

Bringing a replacement station online

Start with the PROFINET device name. The controller uses it to identify the configured station, so a replacement can have an Ethernet connection yet still fail to exchange I/O data if its name is wrong. On this generation, the SIMATIC Micro Memory Card (MMC) also stores the device name.

Next, compare the physical module sequence with the STEP 7 hardware configuration. A mismatch can produce a configuration fault even when the hardware is sound. Use the PLC diagnostic records to distinguish a station communication problem from a fault on an individual module. Recording the original device name, firmware and module arrangement before removal makes the replacement easier to commission.

High Feature, safety I/O and firmware

With suitable fail-safe modules, this interface supports PROFIsafe communication. The F-CPU executes the safety program, while the IM151-3 PN High Feature carries the safety data between the controller and the station. Standard and safety signals can therefore share an ET 200S station.

I/O compatibility also depends on the installed firmware. One specific example is the 6ES7131-4BF00-0AA0 8DI DC24V module: Siemens specifies V4.0.1 or later for use with this interface. When adding I/O to an older station, read the actual firmware version rather than relying on the part number alone.

Replacing a 3BA20 with a 3BA23

The Siemens manual for 6ES7151-3BA23-0AB0 explicitly supports replacing a 3BA20 or 3BA22 without reconfiguring the existing system. It also requires a previously used 3BA23 to be reset to factory settings before it is installed as a spare. This replacement support does not give the older 3BA20 every feature introduced on the newer module.

Manuals and PDF documentation

Visit Siemens ET 200 user manuals for wiring, commissioning and diagnostic documentation. Choose documents that cover the 3BA20 order number. The 3BA23 manual is referenced here specifically for its guidance on replacing the earlier module.

Related topics

I/O modules: digital inputs | digital outputs | analog inputs | special input modules | special output modules.

Station hardware: power supply modules | power distribution modules | terminal blocks | connection modules | additional modules.

Networks: PROFIBUS and PROFINET | other network interfaces.

Technology and safety: counter modules | positioning modules | functional modules | safety modules | PROFIsafe.

Explore ET 200

Simatic ET200 | About Siemens ET200 PLC | Siemens ET200 User Manuals

Technical references: Siemens ET 200S Operating Instructions, A5E00515771-06; PROFINET IO Diagnostics, 24000238; ET 200S Fail-Safe Modules, A5E00103686-08; 8DI DC24V, A5E01077339-02; IM151-3 PN HF (3BA23), A5E01584258-04, page 10.