6ES7 142-6BG00-0AB0

Siemens Main Menu › SIMATIC S7 › ET 200 Modules

Siemens 6ES7 142-6BG00-0AB0 — ET 200eco PN 8-Channel Digital Output Module

6ES7 142-6BG00-0AB0 is an ET 200eco PN field module in the Siemens ET 200 distributed I/O family, providing eight 24 V DC digital outputs. It offers up to 1.3 A per channel and eight M12 load connections. Among ET 200 digital output modules, it serves machine-mounted loads controlled over PROFINET. Its protection rating is IP67.

Check channel current and group totals separately

Total output current is limited to 3.9 A per group up to 60 °C. Four outputs drawing 1.3 A each would total 5.2 A, exceeding that limit. When planning power distribution and potential groups, calculate simultaneous loads together rather than checking each channel in isolation.

The permitted supply range for 1L+ and 2L+ is 20.4–28.8 V DC. When selecting industrial power supplies, account for cable voltage drop and load inrush. If power continues to other field devices, also check the total current passing through the supply connectors.

M12 connections and supply groups

X1–X4 belong to 1L+; X5–X8 belong to 2L+. Each load socket carries one output on pin 4. Select M12 field cables and connectors against the pin assignment. When inspecting connection components and wiring arrangements, match the pins, cable conductors and load; connector diameter alone does not establish compatibility.

Unused sockets require suitable sealing caps to maintain IP67 protection. Inspect mating surfaces, seals and connector tightness. After maintenance, arrange cables without tension or mechanical strain on the connections.

PROFINET and diagnostic settings

This model uses PROFINET IO. When reviewing ET 200 communication interfaces, compare the device name and network settings with the project records. In the SIMATIC S7 hardware configuration, check wire-break, short-circuit and missing-supply diagnostics; their documented defaults are disabled. CPU/master STOP response can be set to switch off or retain the last value.

Five checks before selection

1. Exact model: Confirm ET 200eco PN within the ET 200 system and product families. 6BG00-0BB0 is the 0.5 A version with M12-L power connections; a similar order number does not establish direct interchangeability.

2. Load selection: Record operating voltage, inrush and activation sequence for contactors and coil loads. Maximum lamp load is 5 W.

3. Protection and capacity: Electronic short-circuit protection is provided. However, outputs must not be paralleled to increase current capacity. Meet higher current requirements through suitable output or interface selection.

4. Field test: Verify that commands reach the load and produce the intended operation. Where available, compare running or position feedback from ET 200 digital input modules.

5. Supply scope: Check the label photograph, socket and thread condition, sealing caps and included cables. For used equipment, record the test result and hardware revision.

Editor's Note

If only four outputs stop operating together, inspect the corresponding supply group first. A working network connection does not prove that load power is present. Record which sockets are affected before deciding to replace the device.

PDF manuals and wiring diagrams: Visit the Siemens ET 200 manuals and PDF documents page. Manual A5E01250250-AH, 01/2015 covers connections on page 46, this model on pages 125–129 and parameters on page 140.