6ES7 142-4BD00-0AA0
Siemens automation › SIMATIC S7 › Siemens ET 200 › 6ES7142-4BD00-0AA0
Siemens 6ES7 142-4BD00-0AA0 — ET 200pro 4 DO 24 V DC / 2 A
The 6ES7 142-4BD00-0AA0 is an ET 200pro digital output module within the Siemens ET 200 distributed I/O family. It provides four 24 V DC outputs, each rated at 2 A. When selecting from ET 200 digital output modules, check the complete order number together with the station's ET 200pro configuration.
Output capacity and total load limit
Load supply: 24 V DC, 2L+. Total output current: Siemens' 03/2013 manual specifies 6 A up to 40 °C and 4 A up to 55 °C, in all mounting positions. Loading all four channels at 2 A simultaneously exceeds the total limit. Outputs must not be connected in parallel to increase current capacity.
When assessing ET 200 power supply modules, consider more than the power supply rating. Review the ET 200 power distribution components alongside simultaneous loads, cable voltage drop and the ambient temperature at the station.
Bus module and field connections
Siemens specifies that the bus module is included; the I/O connection module is ordered separately. Compatible options include CM IO 4 × M12 — 6ES7194-4CA00-0AA0 and CM IO 4 × M12P — 6ES7194-4CA10-0AA0. Check the existing label and connector arrangement when selecting ET 200 connection modules.
For these two connection modules, pin 3 is 2M, pin 4 is the output signal and pin 5 is functional earth FE; pins 1 and 2 are unassigned. X1–X4 correspond to DQ0–DQ3. Do not apply this assignment to other connection types. Compatibility also needs separate verification for bases from other series listed under ET 200 terminal blocks.
Distinguish AA0 from the HF version
The 6ES7142-4BD00-0AA0 reports output short circuits to M at module level. The 6ES7142-4BD00-0AB0 is the High Feature version with channel diagnostics and wire-break monitoring. Recording only “4 DO, 2 A” in maintenance records can conceal this difference.
Five checks before selection or replacement
1. Labels and station: Record the complete electronic module number, connection module and ET 200 station configuration. Compare the physical module sequence with the existing hardware configuration.
2. Communication: Identify the complete order number of the PROFIBUS or PROFINET interface. Do not infer station communication from the output module's order number.
3. Signal list: Record command outputs, feedback from ET 200 digital input modules and measurements from ET 200 analog input modules separately. This makes it easier to compare an output command with the actual field response.
4. Loads and wiring: Check each load's operating and starting current, simultaneous operation, the 2L+/2M supply and connector pins. A higher-rated power supply does not increase the module's current limit.
5. Functional test: After replacement, operate outputs in a controlled sequence. Verify that the intended load responds, addresses are correctly mapped and diagnostic entries have cleared.
Editor's note: A valve that fails to operate does not, by itself, prove an output module fault. Record the command bit, load supply, connector condition and valve coil checks together. For problems that appear when several loads switch on, examining total current and supply voltage together can help isolate the cause.
Manuals and PDF documents
Consult ET 200pro Distributed I/O System through the Siemens ET 200 PDF and user manuals page. 03/2013, A5E00335544-08, section 14.4, pages 344–349 covers this model's connections and technical data. In other editions, search by the complete product number rather than relying on the section number.
Related topics
Power and connections: Power supply modules · Terminal blocks · Connection modules · Power distribution modules
Explore the station: About ET 200 · Communication interfaces · ET 200 manuals