6ES7 138-7AA00-0AA0

Siemens automation › SIMATIC S7 › Siemens ET 200 › 6ES7138-7AA00-0AA0

Siemens 6ES7 138-7AA00-0AA0 ET 200iSP Reserve Module

6ES7 138-7AA00-0AA0 is a reserve module that holds a slot for a future electronic module in an ET 200iSP station. Siemens documentation calls it a Reserve Module / Standby Module. Within the Siemens ET 200 distributed I/O family, its purpose is to occupy a reserved slot; it does not automatically take over the function of a failed input or output module.

Where is the vacant slot?

If the electronic-module gap is at the last station slot, a reserve module or suitable slot cover may be fitted. A gap between electronic modules requires a reserve module. When planning the ET 200 station layout, mark future expansion positions on the drawing instead of treating every vacant position as suitable for the same cover.

Terminal module and advance wiring

The reserve module has no connection to the terminal module's terminals, allowing the base to be wired for its future application. Select ET 200 terminal blocks according to the electronic module that will eventually be installed. Use on TM-RM/RM is specified for reserve module product version 3 and later. Record the version shown on the label.

Depending on the future signal type, start your research with ET 200 digital input modules, ET 200 digital output modules or ET 200 analog input modules. These categories cover several ET 200 families, so verify the selected component's ET 200iSP compatibility separately.

Dimensions and product identification

The module measures 30 × 129 × 136.5 mm (width × height × depth) and weighs approximately 180 g. The data sheet lists 0 digital inputs. The product description includes Ex ib IIC T4 Gb and Ex ib I Mb markings. Include future cable routing and maintenance access when planning the reserved position.

Five checks before selection or expansion

1. Order number and version: Read the complete 6ES7138-7AA00-0AA0 order number and product version. For a TM-RM/RM position, the order number alone is insufficient to establish suitability.

2. Future function: Record the signal or device planned for the slot. Before selecting ET 200 connection components, match the field cable, terminal module and intended electronic module on the same drawing.

3. Power budget: Assess ET 200 power supply modules and power distribution components using the requirements of the future active module. Available physical space does not establish that sufficient electrical capacity remains.

4. Hardware project: Record the station interface and software configuration. Expansion methods for systems using PROFIBUS and PROFINET interfaces depend on the installed interface and controller. If considering changes during operation with CiR, review the applicable system requirements separately.

5. Installation conditions: Compare the Ex markings with the installed equipment label, and check enclosure, terminal and field-circuit suitability against the station installation documentation.

Editor's note: Give a reserved slot a purpose, such as “future pressure transmitter” or “valve feedback”, rather than simply labeling it “spare”. Leave a terminal plan and intended module number with that description. When expansion takes place months later, knowing why the position was reserved can save considerable preparation time.

Manuals and PDF documentation

Visit the Siemens ET 200 PDF documentation and user manuals page for ET 200iSP resources. Read the Reserve module (Standby module) section of the ET 200iSP Operating Instructions together with the 6ES7138-7AA00-0AA0 data sheet.

Related topics

Power and connections: Power supply modules · Terminal blocks · Connection modules · Power distribution modules

Explore the station: About ET 200 · Communication interfaces · ET 200 manuals