6ES7 138-4CF02-0AB0

Siemens 6ES7 138-4CF02-0AB0 – ET 200S PM-E F pm PROFIsafe Power Module

Siemens 6ES7 138-4CF02-0AB0 is the PM-E F pm DC24V PROFIsafe fail-safe power module for ET 200S within the SIMATIC ET 200 family. It combines a 10 A relay output switching the P1/P2 potential buses with two 2 A P/M-switching fail-safe digital outputs.

Consider both functions when selecting a power module. Disconnecting a load-group supply and controlling an individual actuator create different wiring and control requirements within the installation.

P1/P2 buses and DO0–DO1 outputs

Start by identifying which loads share the same potential group. The module’s front panel cannot show which valves, lamps or contactors will be affected when that group is switched off. Trace the supply distribution and the connected digital output modules on the same drawing.

When modifying an existing machine, check whether an auxiliary supply introduced elsewhere could affect the intended safety shutdown. The power distribution arrangement belongs in the safety review alongside the control program.

Safety capability depends on the configuration

When standard DO modules are supplied through P1/P2, the manual specifies SIL2 / Category 3 for both the bus output and DO0–DO1. In a suitable arrangement with no modules supplied through P1/P2, DO0–DO1 can achieve SIL3 / Category 4.

The product must therefore not be assigned the same safety capability in every wiring arrangement. Review the safety module, connected loads and safety program together. A component’s maximum capability does not automatically establish the safety level of the complete machine.

The application should clearly define the required stopping function, the hazard being addressed and the conditions for restarting. Confirming that these behaviours remain correct after replacement requires more than observing an output switch on and off.

P/M switching and the load return

P/M switching controls both the positive and return paths of the load. A load-side connection between M and chassis can bridge the M switch in certain supply arrangements and cause short-circuit diagnostics.

During grounding checks, distinguish protective earth from the load’s M reference. Preserve PE continuity while reviewing the load’s internal connections and any EMC components. Adding an arbitrary common connection to suppress a fault can change the intended circuit behaviour.

Siemens identifies improved tolerance to capacitive loads between M and chassis from hardware release 02 of 4CF02. Include the hardware release as well as the order number when requesting a replacement.

Supply voltage and load calculation

The rated supply is 24 V DC, with an allowable range of 20.4–28.8 V DC. Aggregate current limits for horizontal installation are 10 A at 40 °C, 7 A at 55 °C and 6 A at 60 °C. For vertical installation, the limit is 6 A at 40 °C.

When selecting the power supply and wiring, account for more than steady operating current. Consider coil pickup behaviour, simultaneous load operation and cabinet temperature. Measure voltage under load between the relevant supply and return points.

Using an interposing relay does not remove the need for load assessment. Its coil current, suppression device and required release behaviour must suit the application.

Terminal base and protection

The supported terminal bases are TM-P30S44-A0 and TM-P30C44-A0. Electronic module dimensions are 30 × 81 × 52 mm.

Select a terminal block by its complete type, terminal arrangement and existing wiring, rather than width alone. Review other connection modules according to their intended functions.

For relay-contact protection, the manual specifies an external 10 A type-B circuit breaker in the L+ supply. When selecting fuses and protective devices, distinguish protection of the relay path from protection of the electronic outputs.

PROFIsafe addressing, diagnostics and commissioning

The PROFIsafe address, hardware configuration and safety program must agree. Record the existing address settings and project information before replacement to reduce the risk of working with the wrong station or channel.

If the station does not communicate, distinguish the PROFIBUS/PROFINET network status from F-communication diagnostics. Review the PLC diagnostic record, module indicators and field measurements together.

An output held in its safe state does not necessarily indicate failed hardware. Investigate the supply, address configuration, load connections and detected faults. Repeated resets should not replace finding the cause of a recurring problem.

Information for replacement selection

Include the complete 6ES7 138-4CF02-0AB0 reference, hardware release, terminal base and modules connected to the P1/P2 group. Describe whether the problem affects DO0–DO1, the bus-fed load group or the complete station.

After commissioning, verify normal automation system operation together with the response to a safety demand and the permitted restart behaviour.

Editor’s note: “24 V safety power module” is not enough information for a reliable selection. The modules connected to P1/P2 and the arrangement of the load return directly affect fault assessment and the achievable safety capability.

Technical manuals and PDF documentation

The model’s main reference is ET 200S Fail-Safe Modules, A5E00103686-04, section 7.2. Later information concerning the hardware release should also be considered. Visit our Siemens ET 200 manuals and PDF documentation page to explore the documents.

Related topics and product categories

For an introduction to the family, visit About Siemens ET 200. Other station components can be found under functional and safety modules and digital input modules. Verify each component’s suitability for its role in the safety function.

Explore Siemens products: Siemens | Siemens S7 PLC | SIMATIC S7 | ET 200 products