6ES7 138-4CA60-0AB0
6ES7 138-4CA60-0AB0 is a Siemens PM-E DC24V High Feature power module for the SIMATIC ET 200S distributed I/O system. It monitors the load supply for electronic modules within a potential group. Its narrow design and diagnostic functions help organize and monitor cabinet power distribution. Related products are available in our ET200 power supply modules section.
Device Description
An external 24 V DC supply enters the station through a suitable TM-P terminal module. Downstream electronic modules form a potential group; another TM-P supply point can start a separate group. This arrangement allows the load supplies for different machine sections to be organized independently. Consider the roles of power distribution modules and connection modules together when planning the station.
The 10 A rating is the total current-carrying limit for the supplied group. Selecting a higher-rated external power supply does not increase this limit. Calculate the combined demand of the modules and their connected loads, paying particular attention to loads energized simultaneously by digital output modules.
Technical Data
Manufacturer: Siemens
Order Number: 6ES7 138-4CA60-0AB0
Designation: PM-E DC24V HF — High Feature
System: SIMATIC ET 200S
Rated Load Voltage: 24 V DC
Maximum Current-Carrying Capacity: 10 A
No-Load Current Consumption: Maximum 15 mA from L+
Typical Power Loss: 0.35 W
Dimensions: 15 × 81 × 52 mm — width × height × depth
Approximate Weight: 35 g
Installation: On a compatible TM-P terminal module
Indicators: PWR — green; SF — red
The module has no internal short-circuit or overvoltage protection. Assess supply protection, conductor size and load distribution together. Protective-device selection should account for the wiring and connected equipment, rather than relying solely on the module's 10 A rating.
Terminal Module and Connection Selection
Field wiring connects through the terminal base carrying the PM-E. Compatible examples include TM-P15S23-A1 / 6ES7 193-4CC20-0AA0 with screw terminals, TM-P15C23-A1 / 6ES7 193-4CC30-0AA0 with spring terminals and TM-P15N23-A1 / 6ES7 193-4CC70-0AA0 with FastConnect terminals.
Check the AUX bus arrangement as well as the connection method. Bases of the same width may distribute potentials differently. For an existing cabinet, read the complete terminal-base order number and confirm whether the base is included in the purchase. Connection diagrams appear on pages 8 and 9 of the model manual.
High Feature Functions and Configuration
The High Feature version provides load-voltage and feedback-voltage diagnostics, together with status information. With an appropriate configuration, supply conditions can therefore be evaluated through the control system as well as at the cabinet. Monitoring this information in the PLC program can help produce more useful operator messages.
Address-space options:
S: 1 input byte for status.
O: 8 input bytes and 8 output bytes for option handling.
SO: 9 input bytes and 9 output bytes; the ninth output byte is unused.
Option handling supports machine variants within a common project structure. Availability depends on the interface and configuration. Before selecting O or SO, check how the corresponding control and feedback areas are used by the application. Changing the device entry also requires a review of the associated program addresses.
Interface compatibility: Examples of the minimum requirements listed in the manual are V2.2.4 for 6ES7 151-1AA05-0AB0 and V2.2.3 for 6ES7 151-1BA02-0AB0. Consult the compatibility list for other IM151 models. This makes the complete order number of the installed ET200 communication interface an important selection detail.
LED Indicators and Troubleshooting
PWR — Green: Indicates the load supply. Check the supply circuit if it is off.
SF — Red: Indicates a group fault or diagnostic condition; evaluate it with the online diagnostics.
Error type 17 — Decimal: Associated with missing sensor or load voltage; its binary representation is 10001.
Missing-load-voltage diagnostics are disabled by default. The status byte continues to update independently of that setting. Consequently, established communication alone does not confirm that the application's supply alarm has been configured; check both the parameter and the alarm logic.
If several modules report faults together, start by examining their common supply point. Measure at both the DIN rail power supply and the terminal base while the load is operating. For a fault affecting only one channel, separately inspect the relevant sensor, load, and cables and connectors.
Installation and Commissioning Recommendations
Document group boundaries: Mark which electronic modules receive their supply through each PM-E. When adding equipment, check the existing group load as well as the available slot space. Clear identification of cabinet connections makes later measurements and maintenance easier.
Test under operating conditions: Follow the initial no-load measurements with an observation of the normal machine sequence. Include moments when relays and other loads operate together. If a fault occurs only during a particular action, correlate the measurements with that action before replacing components.
Complete the replacement record: Keep the PM-E label, TM-P base number, IM151 firmware version and project backup together. During recommissioning, verify the supply indicators, online diagnostics and status addresses used by the application.
Editor's Recommendations and Related Topics
Compare the complete order number when purchasing a spare. The PM-E family includes different voltage ratings and diagnostic features, so appearance alone is an unreliable selection method. Also confirm the delivery scope rather than assuming that a terminal base shown in a photograph is included.
For other station components, browse our digital input modules, analog input modules and Siemens ET200 products. These categories contain several ET200 subfamilies; check ET 200S compatibility for each selected item.
Our explanation of PROFIBUS and PROFINET provides background on station communication. For safety applications, review the relevant ET200 safety modules and PROFIsafe information. The HF designation of this product does not itself specify a safety rating.
Manuals and Technical Documents
+ Siemens ET200 User Manuals — PDF archive page
+ Siemens 6ES7 138-4CA60-0AB0 Manual — model-specific English PDF
+ Siemens ET 200S System Manual — installation, potential groups and general wiring
+ Siemens ET200 General Catalogue — general product-family PDF
Technical sources: Siemens model data sheet, Siemens ST 70 PM-E and terminal selection section and IM151-1 FO STANDARD option-handling documentation. The first two links are Siemens documents hosted externally.
++ Siemens Automation Main Page >
++ Siemens Automation Contact — for Otomasyon AVM
++ About Siemens ET200 PLC >
Reminder: Please confirm current availability, condition and delivery scope for Siemens 6ES7 138-4CA60-0AB0 and other SIMATIC products with Otomasyon AVM. Some devices are used products; take this into account when purchasing. Products will not be restocked once sold out. This page provides general information; the product label, hardware revision and applicable manufacturer documentation should govern your application.
Note: Manuals, commissioning recommendations and troubleshooting explanations are non-binding and may be updated or improved. The Otomasyon AVM Community welcomes practical experience. You can share your operating and maintenance recommendations with us.