6ES7 138-4CA00-0AA0
Siemens 6ES7 138-4CA00-0AA0 – ET 200S PM-E 24 V DC Power Module
Siemens 6ES7 138-4CA00-0AA0 is a PM-E power module with 24 V DC load voltage monitoring for SIMATIC ET 200S stations. It supervises the supply shared by the electronic modules in its potential group and supports reporting a missing load voltage to the control system. Within the Siemens ET 200 family, this model is relevant to maintenance of existing ET 200S installations and distributed I/O stations using compatible 24 V DC modules.
The PM-E’s Role in an ET 200S Station
A potential group contains electronic modules sharing a common load supply. Power enters through a suitable TM-P terminal module, while the PM-E monitors the group’s load voltage. This allows the station’s supply arrangement to follow the different sections of a machine. When selecting ET 200 power modules and power distribution components, consider which modules and loads belong to each group.
An external power supply provides the required 24 V DC. PM-E selection depends on voltage, terminal compatibility and diagnostics. Selection of the associated DIN rail power supply also needs to account for total consumption and operating conditions.
24 V DC Supply and 10 A Group Capacity
The rated load voltage is 24 V DC, with a specified maximum current-carrying capacity of 10 A up to 60 °C. This limit applies to the total current carried by the supply group. The module draws up to 4 mA from L+ without load, with a typical power loss of 0.1 W. Reverse polarity protection is provided.
Valves, relays and contactor coils controlled through digital output modules may operate simultaneously. Include that combined demand in the calculation and check each output channel’s individual rating. Station mounting and ambient conditions must also meet the system manual’s requirements.
External Protection and Supply Wiring
The 6ES7 138-4CA00-0AA0 has no internal short-circuit protection. External protection is required for the supply circuit; Siemens specifies a type C tripping characteristic in its data sheet. Selection of suitable fuses or circuit breakers should consider DC suitability, conductor size, load current and the power supply’s short-circuit response. A 10 A group capacity does not establish the correct protection rating for every field cable.
Loose supply connections or excessive voltage drop can affect several modules together. Comparing the source voltage with the voltage reaching the station helps locate the affected part of the circuit during maintenance.
Load Voltage Diagnostics and Indicators
The green PWR LED indicates load voltage status, while the red SF LED indicates a group fault. The missing load voltage diagnostic can be enabled through a parameter. Module status is updated in the process input image status byte independently of that diagnostic setting. This information can support fault evaluation in the PLC program.
Give each supply group a clear name on the HMI or SCADA display. An alarm such as “Packaging station sensor supply” tells maintenance personnel which circuit to investigate. Matching that description to the physical station label is particularly useful in larger cabinets.
Terminal Modules and Cabinet Layout
Siemens connection examples include TM-P15S23-A1, TM-P15S23-A0 and TM-P15S22-01 terminal modules. Selection depends on the required AUX1 arrangement and available connection points. Recording the complete codes of the installed ET 200 terminal blocks and connection modules makes replacement selection more straightforward.
The PM-E body measures 15 × 81 × 52 mm and weighs approximately 35 g. Overall installed dimensions depend on the terminal module. Galvanic isolation separates the load supply from the backplane bus. Cable routing and grounding arrangements should be reviewed alongside the cabinet drawings.
Applications and Replacement Selection
A supply plan may include compatible digital input modules connected to 24 V DC sensors and photoelectric sensors, together with suitable output modules. Station communication is determined by the installed interface module.
Siemens identifies 6ES7138-4CA01-0AA0 as the successor to this model. When planning a replacement, compare the hardware configuration, terminal module and diagnostic settings. Keeping the project backup alongside a record of the installed module label gives purchasing and maintenance teams a shared reference.
Editor's Advice
If several inputs or outputs develop problems together, check whether they share the same PM-E group. The external protection device, 24 V supply or terminal connections may be the common cause. Comparing the indicators with project diagnostics before selecting a spare can help avoid unnecessary module replacements.
Technical Documents and Related Topics
Visit our Siemens ET 200 manuals and PDF documents section for wiring diagrams and parameter descriptions. Check that the PM-E order number in the document matches the installed module.