6ES7 134-4NB50-0AB0
6ES7 134-4NB50-0AB0 – Siemens ET 200S 2AI RTD High Feature
6ES7 134-4NB50-0AB0 is a two-channel RTD and resistance input module for Siemens ET 200S. Designated 2AI RTD High Feature, this 15 mm wide electronic module transfers measurements from resistance temperature sensors to the control system. Browse temperature sensors for probe options.
Measurement types and resolution
Supported sensors include Pt100, Pt200, Pt500 and Pt1000, as well as Ni100 and Ni1000. Resistance ranges are 150 Ω, 300 Ω, 600 Ω and 3000 Ω. RTD resolution is specified as up to 15 bits plus sign. Select the sensor type, temperature coefficient and measuring range together.
Sensor wiring and terminal selection
Pt/Ni sensors support 2-, 3- and 4-wire arrangements. Lead resistance is automatically compensated with a 3-wire connection. Check the installed wiring against the sensor diagram instead of identifying the connection solely by conductor colours.
The manual shows TM-E15S24-01 and TM-E15S26-A1 for 4-wire connections. Check the complete type code and terminal functions when selecting the terminal block. When reviewing other connection modules, remember that equal module widths do not establish identical terminal arrangements.
Supply and station arrangement
The module receives its 24 V DC load supply through the ET 200S power module. Record the electronic module, terminal block and power-group order numbers together before ordering.
The station’s interface module connects ET 200S to the higher-level network. IM 151-1 High Feature is a PROFIBUS example, while IM 151-3 PN High Feature is a PROFINET example. Match the PROFIBUS or PROFINET arrangement and hardware revisions to the existing project. Browse ET 200 analog and interface modules for station options.
Diagnostics and commissioning
A front-panel SF LED indicates group faults. Group diagnostics, underflow/overflow and wire-break diagnostics are configurable and disabled by default. Check the diagnostic settings and fault reporting for the channels in use during commissioning.
Distinguishing similar order numbers
6ES7 134-4NB00-0AB0 is a thermocouple input module. 6ES7 134-4MB02-0AB0 handles current inputs. Verify the actual sensor signal alongside the complete order number when selecting a spare.
For a used unit, inspect nameplate legibility, electrical contacts and mechanical latches. Ask which sensors or reference resistors were used to test both channels and at which measurement points. A power-on check alone does not establish measurement performance.
Editor’s Note: A Pt100 marking on the probe does not necessarily mean that the PLC receives a direct RTD connection. If a 4–20 mA transmitter is fitted in the sensor head, the PLC needs a current input. Check the sensor head, destination terminals and channel settings together before ordering the module.
Manuals and PDF documents
Use the Siemens ET 200 manuals section for documentation. The 12/2004 ET 200S manual, Section 12.15, printed pages 12-82–12-89, covers this exact model. Channel parameters are on pages 12-34–12-37. Search the document for the complete code 6ES7 134-4NB50-0AB0.
Related topics
Browse temperature controllers for temperature applications, and PLC and HMI, PLCs and modules, Siemens S7-300 and S7-300 CPU modules for other control-system components. Base hardware selection on the installed station and its project documentation.
Navigation
Siemens ET 200 | Siemens SIMATIC S7 | Siemens automation | OtomasyonAVM home