6ES7 134-4JB50-0AB0
6ES7 134-4JB50-0AB0 – Siemens ET 200S 2AI RTD Standard
6ES7 134-4JB50-0AB0 is a two-channel RTD and resistance input module for Siemens ET 200S. Designated 2AI RTD Standard, this 15 mm wide module measures temperature through directly connected Pt100 and Ni100 sensors. Browse temperature sensors for probe options.
Sensor options and resolution
Pt100 and Ni100 have standard and climatic measuring ranges. Resistance ranges are 0–150 Ω, 0–300 Ω and 0–600 Ω. RTD resolution is 15 bits plus sign; resistance resolution is 14 bits for 150 Ω and 15 bits for 300 and 600 Ω.
Two-, three- and four-wire connections
Four-wire wiring separates the constant-current and measuring leads. Two- and three-wire connections require appropriate terminal bridges, and lead resistance is included in the measurement. This model’s three-wire connection does not provide automatic lead-resistance compensation. The wiring arrangement affects the result, particularly with long sensor cables.
The manual’s terminal module examples are TM-E15S24-01 and TM-E15S26-A1. Compare the installed connection components and bridges with the diagram for the sensor’s wire count.
Supply and ET 200S station
The module receives its 24 V DC load supply through the ET 200S power module. The inputs are isolated from the backplane bus and load supply; there is no galvanic isolation between channels.
The interface module connects the station to the PLC. IM 151-1 High Feature is a PROFIBUS example, while IM 151-3 PN High Feature is a PROFINET example. Assess the network arrangement and hardware revisions against the existing project. Browse ET 200 analog and interface modules for other options.
Measurement timing
Conversion takes 110 ms per channel with 60 Hz interference suppression or 130 ms with 50 Hz suppression. The module cycle is the active channel count multiplied by that conversion time. Assess the required process response together with the filter settings.
Diagnostics and wire-break limitation
The red SF LED indicates a group fault. Group, underflow/overflow and wire-break diagnostics are disabled by default. Wire-break diagnostics monitor only the constant-current leads. In three- and four-wire connections, breaks in the M+ and M− measuring leads are not detected; undefined measurement values can result.
Related models and spare selection
6ES7 134-4NB50-0AB0 is the High Feature RTD version. 6ES7 134-4MB02-0AB0 is a current input module, relevant where a sensor signal has been converted to 4–20 mA, for example. Check the sensor label and the signal reaching the PLC together.
Siemens documents 6ES7 134-4JB51-0AB0 operating in compatibility mode configured as JB50. In this mode, however, the DS1 diagnostic record increases from 16 to 24 bytes, and the channel count reported in the record changes. Review the program that processes diagnostic data and the manufacturer’s compatibility section before replacement.
For a used unit, inspect the nameplate, contacts and latches. Request a test record identifying the reference resistances and wiring arrangements used to check both channels.
Editor’s Note: If the temperature reading has a persistent offset, check the sensor type, cable joints and terminal bridges before replacing the module. Applying the same reference with a suitable RTD simulator at the module input and at the far end of the field cable can help assess the cable’s effect on the measurement.
Manuals and PDF documents
Documentation is available through the Siemens ET 200 manuals section. The 12/2004 ET 200S manual, Section 12.14, printed pages 12-78–12-81, covers JB50 directly; parameters appear on pages 12-32–12-33. For transition to JB51, see page 15 of the 07/2008 manual A5E01076865-02.
Related topics
Browse temperature controllers for temperature applications, and PLC and HMI, PLCs and modules and Siemens S7-300 for other system components.