6ES7 138- 4AA11-0AA0

6ES7 138-4AA11-0AA0 — Siemens ET 200S 30 mm RESERVE placeholder module

Series: Siemens SIMATIC DP. Category: ET 200S RESERVE module.

6ES7 138-4AA11-0AA0 is a 30 mm RESERVE module that keeps an ET 200S slot available for a future electronic module. It provides no input or output channels. It supports planned machine expansion by preserving a module position that is not yet needed in the installed configuration.

Dimensions and terminal selection

Dimensions are 30 × 81 × 52 mm (width × height × depth), approximate weight is 55 g, and typical power dissipation is 0.025 W. 6ES7 138-4AA01-0AA0 is 15 mm wide; the 4AA11 model on this page is 30 mm wide. This order-number difference should not be treated simply as a revision change.

Use a suitable 30 mm TM-E terminal module. The RESERVE module does not connect to the terminal’s field contacts, allowing wiring for the future electronic module to be prepared in advance. Select terminal blocks and connection components with the future module’s wiring diagram in mind.

Address space and diagnostic behavior

Address space must match the planned electronic module. In Siemens’ method without option handling, configure the future module and enable the interface parameter “Operation at preset <> Actual configuration”. The interface can then indicate SF and 10B: Wrong module. The RESERVE module has no status indicator or diagnostic function of its own.

In this method, configured digital inputs return the substitute value 0, while analog inputs return 7FFFH. These are not field measurements. RESERVE is also unsupported with IM151-1 Standard 6ES7 151-1AA00-0AB0.

Option handling and expansion

Option handling manages the relationship between a machine’s maximum hardware configuration and the modules actually installed. RESERVE use depends on interface support, firmware and correct configuration. For PROFINET applications, assess slot assignment and the control data record. Inserting the module alone does not activate this function.

Do not assume identical settings across PROFIBUS and PROFINET or other network interfaces. Record the existing project and station order before making changes. “RESERVE” does not mean an actively redundant I/O channel, and this module does not provide power supply or power distribution functions.

Editor’s note: An unlit RESERVE module is not, by itself, evidence of a fault. Compare the full order number, 30 mm terminal width and the module assigned to that position in the project. If SF is present, read the interface diagnostics. During expansion, check the new electronic module’s addresses and field wiring together; do not use substitute input values as actual process data.

PDF documentation and manuals

For selection and configuration, read the RESERVE module manual alongside the manual for the installed IM151 interface. Visit the Siemens ET 200 PDF and user manuals page for relevant documentation.

Related topics

When reviewing an ET 200 system, compare the positions assigned to digital inputs, digital outputs and function modules against the project. Select counter modules and positioning modules according to the required signal type and application function.

In applications involving safety modules and PROFIsafe, RESERVE does not provide a safety function. Assess the suitability of additional modules and accessories using each product’s complete order number.