6ES5 947-3UR21

Siemens 6ES5 947-3UR21 – S5-155H CPU 947R Processor Module

Siemens 6ES5 947-3UR21 is the CPU 947R module for S5-155H in the SIMATIC S5 family. It forms part of the 946R/947R processor assembly together with CPU 946R. Assessment of this component in an S5 system must include its companion processor and the installed redundant central-controller arrangement.

The Siemens comparison table specifies 128 KB of fixed RAM for the 946R/947R architecture, expandable through cartridges in 355 memory modules to 896 KB total user memory. This maximum does not establish the actual capacity fitted to an individual assembly; inspect the installed memory configuration separately.

Checking the memory configuration

Record the references of the S5 memory modules and cartridges installed in the 355. For memory options such as 6ES5 375-0LA21 and 6ES5 375-0LA41, check capacity, RAM/EPROM type and the applicable 355 arrangement together. Physical insertion alone does not establish suitability.

Keep the program backup, data blocks and installed-memory inventory in the same service record. Record fixed RAM and expanded total memory separately. A capacity shown in an old backup should not be assumed to describe the hardware currently installed.

S5-155H central-controller and slot arrangement

The Siemens S5-155H central-controller table shows positions 11 and 19 for CPU 946R, and 27 for CPU 947R. Match these to the rack markings and the applicable central-controller documentation. Do not transfer the arrangement to another rack without verification.

Assess both central controllers and their interconnection as part of the redundancy arrangement. Record the positions of IM 324R and the interface modules against the installed drawing. Establish differences in modules, cabling and versions between the master and standby sides before replacing a CPU component.

Programming and PG access through a CP

Use the appropriate STEP 5 project and CPU 946R/947R programming information. Select the programmer cable and connection arrangement for the installed system. When communication fails, check software version, connection path and system state separately.

The Siemens CP 1430 TF backplane-communication table specifies CPU version 06 for 6ES5 947-3UR21 and PG software V6.3. For PG access over SINEC H1, assess these requirements together with the appropriate CP and configuration. The 3UR21 reference alone does not establish that this access is available.

Distinguishing related references and processor assemblies

Do not automatically treat 6ES5 947-3UR11, 6ES5 947-3UA21 or 6ES5 947-3UA22 as interchangeable with 3UR21. Read memory and program-loading information for CPU 948R within its own hardware scope. Establish replacement suitability from the complete reference, version and installed system arrangement.

Power and peripheral checks

Inspect the S5-155H power supply, backplane connections and contacts. Obtain supply requirements from the applicable power-supply and module documentation rather than transferring another CPU’s consumption figures. Treat voltage measurements and processor functional tests as separate checks.

Trace digital-input, digital-output and analog-module faults through addresses, wiring and diagnostic records. Before replacing the processor assembly, establish whether the fault lies in the CPU, memory, supply or peripheral connection.

Editor’s Note

Check the companion 946R reference and installed system arrangement as well as the 947R label. With used Siemens processors, powering one board does not demonstrate operation of the complete processor assembly.

Obtain photographs and references for the memory cartridges. Does the advertised total match the installed memory? Establish that before assuming a large application will fit.

If access through a CP is required, inspect the CPU version label first. Overlooking the version requirement for PG communication can lead to unnecessary cable changes and lengthy troubleshooting.

Do not test the board in an arbitrary slot. Use the correct rack, position and processor assembly so that the test is meaningful and the hardware is protected.

In Siemens S5 maintenance, record the program and present state before intervention. Do not perform an overall reset without a backup. For a unit described as tested, ask which assembly, program and functions were used in the test.

OtomasyonAVM resources and PDFs

Start with the 6ES5 947-3UR21 product page, CPU 946R and the SIMATIC S5 overview. Use the OtomasyonAVM S5 PDF archive to locate relevant documentation. Consult the S5-155H central-controller and CPU 946R/947R programming sections of the English S5-155U CPU 946/947 manual. Section 1.8 of the CPU 948R guide is referenced here specifically for its comparison of the older and newer memory architectures.