6ES5 581-0EA11

Siemens 6ES5 581-0EA11 – CP 581 386 Basic Board with 4 MB RAM

Siemens 6ES5 581-0EA11 is a CP 581 basic computer board developed for Siemens S5 PLC systems. Installed in the SIMATIC S5 rack, this version features a 25 MHz Intel 80386SL processor and 4 MB DRAM working memory. Its defining order-number distinction is that it has no onboard silicon disk.

The CP 581 handles computer tasks such as processing process records, storing production information and managing machine data. The S5 CPU executes the control program while the CP 581 handles data processing. When reviewing S5 communications modules or S5 special modules, assess the operating system, application and connected storage alongside the board hardware.

4 MB working memory and boot media

The 4 MB specification describes RAM, not disk capacity. Because 0EA11 has no onboard silicon disk, identify the medium from which the existing system boots. The CP 581 architecture supports suitable memory cards or a separate mass storage module. When selecting from S5 memory cards, check CP 581 support and the software requirements as well as capacity.

The closest distinction is 6ES5 581-1EA11, which includes an onboard silicon disk. 6ES5 581-0EB11 and 6ES5 581-1EB11 belong to the 486-based CP 581 family. Similar front panels do not establish interchangeability between processor generations or between versions with and without an onboard silicon disk.

Storage and AT expansion

Within the CP 581 family, 6ES5 581-0LA11 and 6ES5 581-1LA11 are storage components separate from the basic board. When assessing a spare, record the accompanying disk module and connecting parts. Verify the fitted disk capacity, software contents and suitability for the basic board against the actual installation.

For installations requiring a short AT board, the manual lists the 6ES5 581-0RA11 slot module for the 386-based CP 581. 6ES5 581-0RA12 is specified for the CP 581/486. Check the expansion board, slot module and mechanical connections together; a board fitting into a connector does not establish compatibility.

CPU connection and peripherals

PLC-side data exchange takes place over the S5 backplane bus. Computer connections include COM 1/3, KEYB/COM 2 and monitor connections. Keep the CP 581 role distinct from that of S5 interface modules. When selecting S5 cables and connectors, use the appropriate Y adapter and the manufacturer pin assignments.

Commissioning requires the rack position, BIOS/SETUP configuration, boot drive and CPU-side communication settings to be considered together. Record RUN, STOP, FAULT and SD-BUSY indications separately. Reaching the BIOS screen, booting the operating system and exchanging data between the machine application and CPU are different verification stages.

System compatibility and replacement selection

The CP 581 manual covers S5-115U, S5-135U, S5-155U and S5-155H systems. Verify the S5 rack and permitted slot arrangement. S5-115U installation requires an adapter casing and a 5 V/15 A S5 power supply. Use with CPU 921 in an S5-135U system is not permitted.

If replacement by another CP 581 version such as 6ES5 581-1EB12 or 6ES5 581-1EC12 is being considered, compare the BIOS, application software and expansions as well as the processor generation and storage arrangement. A later order number does not automatically provide a ready-to-use spare for the existing machine.

Prepare the maintenance record using the system-identification approach in About Siemens S5 PLC. When assessing Siemens automation spares, request the full nameplate, board revision, boot medium, fitted accessories and a backup of the existing software together. These records help identify missing steps after a component change.

Editor's Note

The first practical point is that 0EA11 has no onboard silicon disk. A bare replacement board should not be expected to boot the old installation by itself. Identify the existing boot medium and locate the memory card or disk module before proceeding.

The 4 MB marking describes working memory; it does not show where the machine files are stored. Locate the software medium and back it up while it remains readable. Preserve that backup before formatting a drive or reinstalling software.

If a picture appears but the application does not start, avoid immediately condemning the board. Check the boot drive, disk readability and startup files. Photograph the existing settings first so that troubleshooting does not erase the record of the original configuration.

For display or keyboard problems, also inspect the monitor, cable and Y adapter. Bent pins and loose contacts in older connectors can cause misleading symptoms. Verify a cable’s suitability rather than relying on the connector shape alone.

Finish with the machine’s actual tasks: does the application start, exchange data with the CPU and read its records? A meaningful spare-part assessment includes operation with the existing software and storage, as well as a successful board startup.

OtomasyonAVM resources and PDF files

Browse S5 expansion modules for other components and the S5-115 PDF files archive for shared documentation. Use a manual revision covering the 386-based CP 581 for technical checks.

Related topics

6ES5 581-1EA11 · 6ES5 581-0EB11 · 6ES5 581-1EB11 · 6ES5 581-0LA11 · 6ES5 581-0RA11

S5 section menu

Siemens S5 PLC · SIMATIC S5 · S5 racks · S5 power supplies · S5 cables and connectors · S5 memory cards

External references

Siemens CP 581 Manual, Volume 1 – manufacturer manual (archived copy). Exact code and version without onboard silicon disk: pp. 0-2, 2-5 and 6-3; 386 basic board: p. 3-6; processor and RAM: p. 4-6; memory card and storage: pp. 1-4 and 3-72; system installation: pp. 2-39–2-42.