6ES5 431-8FA11

Siemens 6ES5 431-8FA11 — 8-Channel 24 V DC Failsafe Input Module for S5-95F

The Siemens 6ES5 431-8FA11 provides eight safety-related 24 V DC digital inputs for the S5-95F in the SIMATIC S5 family. Within the S5 digital input range, it is a failsafe F-type module. Its inputs are galvanically isolated by optocouplers in one group of eight.

For safety functions in a Siemens S5 PLC installation, one module is required in subunit A and one in subunit B, with two-channel operation configured using COM 95F. A module pair provides eight failsafe inputs. Assess the rack and module arrangement, paired modules and project parameters together.

24 V DC inputs and sensor requirements

Nominal input voltage is 24 V DC. Logic 0 is specified at −30 to +5 V, and logic 1 at +13 to +30 V. Typical logic-1 current is 9 mA at 24 V. Voltages outside the defined ranges should not be treated as valid input signals.

Check the PNP/NPN output arrangement and the sensor’s suitability for the safety application separately. The manufacturer permits two-wire BERO sensors with a residual current of 1.5 mA. Electrical compatibility alone does not establish the sensor’s approval for the safety function.

Input delay, isolation and power

Typical input delay is 3 ms for both 0 → 1 and 1 → 0 transitions. This is the module’s input delay; the machine’s complete safety response time requires separate assessment. Maximum specified unshielded cable length is 200 m. Isolation in a group of eight does not mean that individual channels are isolated from each other.

Maximum consumption from the internal CPU +9 V rail is 70 mA, with typical module power loss of 2.6 W. Track the S5 power supply and field 24 V supply separately. Where the expansion includes a 700-8FA11 bus unit and, if fitted, a 316-8FA12 interface, check the arrangement against the existing S5-95F project.

Terminal connections and channel order

Connect L+ to terminal 1 and M to terminal 2. Channel order at the bus-unit terminals and wiring does not follow a simple ascending terminal sequence. Do not use protective grounding in place of the M signal reference.

The manufacturer’s channel → terminal mapping is .0 → 4, .1 → 3, .2 → 6, .3 → 5, .4 → 8, .5 → 7, .6 → 10, .7 → 9. Read the channel marking and terminal number together; adjacent terminals do not necessarily represent consecutive channels.

A/B pairing and program addresses

In S5-95F addressing, subunit A uses even-numbered slot n and its partner in subunit B uses n+1. Reference failsafe inputs in the PLC program through subunit A’s even-numbered byte address. For example, with the A: 2 / B: 3 pairing, the input bits are I 2.0–I 2.7 in English operand notation.

The manufacturer does not permit word access to failsafe external I/Os; use the appropriate bit or byte access. During troubleshooting, check DB1 parameters and subunit pairing as well as channel states. Assess the system’s 450-8FA11 failsafe output module according to its own output function and wiring requirements.

Differences from the 8MA11 and similar modules

The 431-8MA11 is a standard eight-input 24 V DC module and cannot replace the 431-8FA11’s safety function. The 421-8MA12 is a standard eight-input, non-isolated module. Matching channel count and voltage does not provide the F function.

The 431-8MC11 is rated for 115 V AC/DC, and the 431-8MD11 for 230 V AC/DC. These are not direct equivalents of the 24 V DC failsafe module either. Use the complete 431-8FA11 order number and the system’s safety configuration when selecting a spare.

Editor’s note

Give the FA letters their proper attention. Having another eight-input 24 V board on the shelf does not mean it can perform this job. Start with the label, then identify the matching A/B module and the project record.

Two fitted modules do not automatically mean sixteen failsafe inputs. Here, the two sides work together to evaluate the same eight inputs safely. A note of each module’s subunit and paired address is valuable when replacing a spare.

Record both channel and terminal numbers before disconnecting wires. On this model, channel .0 goes to terminal 4 and channel .1 to terminal 3. A mistaken sequence can make sound hardware look faulty.

An illuminated LED is only part of the check. Verify that both subunits evaluate the event correctly and that the machine gives the intended response. The safety chain’s behavior matters as much as seeing the input arrive.

For a used Siemens purchase, request clear photographs of the label, revision, connectors and board surface. All eight channels of the used digital input module should be checked; its safety function also requires assessment in a suitable S5-95F arrangement. Keep the bench check and the machine’s safety validation as separate records.

OtomasyonAVM resources and PDFs

+ OtomasyonAVM S5-115 PDF archive. Use the S5-95F manual below for this product’s wiring, addressing and safety functions.

Related topics

+ 431-8MA11 · 421-8MA12 · 431-8MC11 · 431-8MD11 · 450-8FA11 failsafe output · 700-8FA11 bus unit.

Browse SIMATIC S5

+ S5 digital input modules · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLCs · Used digital input modules · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-95F manual — EWA 4NEB 812 6220-02; sections 5.5–5.5.1: two-channel operation and paired modules; chapter 6: addressing; appendix A-7: exact 431-8FA11 technical table and terminal drawing.

+ Siemens ST 50, 1998 — printed pages 2/28–2/29: 431-8FA11 specifications, S5-95F-only note and front connection view; externally archived Siemens publication.