Toshiba H7 Fault codes 2
DC Fuse Open
- Internal DC bus fuse is open.
Solution:
- Check the fuse and replace if necessary.
Dynamic Braking Resistor Overcurrent
- Inability to discharge bus voltage during regeneration.
- No dynamic braking resistor (DBR) installed.
- Deceleration time is too short.
- Improper DBR setup information.
- Defective IGBT7 (or IGBT7 circuit).
- 3-phase input voltage above specification.
Solutions:
- Install a DBR.
- Extend the deceleration time.
- Check DBR setup information and ensure it is correct.
- Check IGBT7 and replace if necessary.
- Check the 3-phase input voltage and ensure it is within the specified range.
Dynamic Braking Resistor Overload
- Deceleration time is too short.
- DBR settings need adjustment.
- Overvoltage Stall settings need adjustment.
Solutions:
- Extend the deceleration time.
- Check and adjust DBR settings.
- Adjust Overvoltage Stall settings.
Earth Fault
- Ground fault at the motor.
- Ground fault at the ASD output.
- Current leakage to Earth Ground.
Solutions:
- Check motor ground connections.
- Check ASD output ground connections.
- Inspect and resolve any current leakage to Earth Ground.
EEPROM Data Fault
- EEPROM read malfunction.
Solution:
- Check the EEPROM and replace or reprogram if necessary.
EEPROM Fault
- EEPROM write malfunction.
Solution:
- Check the EEPROM and replace or reprogram if necessary.
Emergency Off
- Emergency Off command received via EOI or remotely.
Solution:
- Check the source of the Emergency Off command and restart the system if needed.
Encoder Loss
- Encoder signal missing during closed-loop operation.
Solution:
- Check encoder connections and signals to ensure proper operation.
Flash Memory Fault
- Flash memory malfunction.
Solution:
- Check the flash memory and replace if necessary.
Gate Array Fault
- Defective Gate Array or Gate Array malfunction.
Solution:
- Check the Gate Array and replace if necessary.
Input Phase Loss
- Low or missing 3-phase input to the ASD.
Solution:
- Check the 3-phase input voltage and ensure it is present and within the specified range.
Load Drooping
- Load requirement exceeds the motor's capacity.
Solution:
- Reduce the load or increase the motor's capacity.
Load End Short Circuit
- Improper wiring from the ASD output to the motor.
Solution:
- Check the wiring and ensure proper connections.
Low Current
- Improper low current detection level setting.
Solution:
- Check and adjust the low current detection level setting.
Main Board EEPROM Fault
- Internal EEPROM malfunction.
Solution:
- Check the EEPROM and replace or reprogram if necessary.
Motor Overload
- V/f setting needs adjustment.
- Motor is locked.
- Continuous operation at low speed.
- Load requirement exceeds the motor's capacity.
- Startup frequency setting needs adjustment.
Solutions:
- Check and adjust the V/f settings.
- Ensure the motor is not locked.
- Limit continuous operation at low speeds.
- Reduce the load.
- Adjust the startup frequency settings.