Omron VFD Fault code 2
Hello, you are on the Error Codes page 2.
<< Click here for the first page.
-------------------------
Fault Detection (Fatal Errors)
The Inverter will detect the following faults if the Inverter or motor burns or the internal circuitry of the Invertermal functions. When the Inverter detects a fault, the fault code will be displayed on the digital operator, the fault contact (relay) output will operate, and the Inverter output will be shut off causing the motor to coast to a stop.
The stopping method can be selected for some faults, and the selected stopping method will be used with these faults. If a fault has occurred, refer to the following table to identify and correct the cause of the fault. Use one of the following methods to reset the fault after restarting the Inverter. If the operation command is being input, however, the reset signal will be ignored.
The refore, be sure to reset the fault with the operation command turned OFF.
S Turn ON the fault reset signal. Amulti-function input (n050 to n056)must be set to 5 (Fault Reset).
S Press the STOP/RESET Key on the Digital Operator.
S Turn the main circuit power supply OFF and then ON again.
oPE01: incorrect Inverter capacity setting
The Inverter capacity setting doesn't match the Unit. Check parameter o2-04 for the correct setting.
oPE02: Parameter setting range error The parameter setting is outside of the valid setting range.
oPE03: Multi-function input selection error
One of the following errors has been made in the multi-function input (H1-01 to H1-05) settings:
• The same setting has been selected for two or more multi-function inputs.
• An up or down command was selected separately. (They must be used together.)
• The up/down commands (10 and 11) and Accel/Decel Ramp Hold (A) were selected at the same time.
• Speed Search 1 (61) and Speed Search 2 (62) were selected at the same time for a digital input.
• External Baseblock NO (8) and External Baseblock NC (9) were selected at the same time.
• The up/down commands (10 and 11) were selected while PI Control (b5-01) was enabled.
• The emergency stop command NO and NC have been set at the same time.
oPE05: Option Card selection error
The Option Card was selected as the frequency reference source by setting b1-01 to 3, but an Option Card isn't connected.
oPE09: PI control selection error
The following settings have been made at the same time.
• b5-01 (PI Control Mode Selection) has been set to a value other than 0.
• b5-15 (PI Sleep Function Operation Level) has been set to a value other than 0.
• b1-03 (Stopping Method Selection) has been set to 2 or 3.
oPE10: V/f data setting error
Parameters E1-04, E1-06, E1-07, and E1-09 do not satisfy the following conditions:
• E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
• E3-02 (FMAX) ≥ E3-04 (FA) > E3-05 (FB) ≥ E3-07 (FMIN)
oPE11: Parameter setting error
One of the following parameter setting errors exists.
• C6-05 (Carrier frequency Gain) > 6 and C6-03 (Carrier Frequency Upper Limit) <
C6-04 (Carrier Frequency Lower Limit)
• Upper/lower limit error in C6-03 to 04.
Err: EEPROM write error
A verification error occurred when writing EEPROM.
• Try turning the power supply off and on again.
• Try setting the parameters ag
Er-01: Motor data error
There is an error in the data input for autotuning.
There is an error in the relationship between the motor power and the motor rated current.
• Check the input data.
• Check the capacity of the Inverter and motor.
• Check the motor rated current.
Er-02: Alarm A minor fault occurred during autotun-ing.
• Check the input data.
• Check wiring and the machine.
• Check the load.
Er-03: STOP key input The STOP key was pressed to cancel autotuning.
Er-04: Line-to-line resis-tance error
Autotuning was not completed in the specified time.
The results of autotuning has exceeded the setting range for a user parameter.
• Check the input data.
• Check motor wiring.
• If the motor is connected to the machine, disconnect it.
End3: Rated current setting
alarm* The rated current is set too high. Check the input data (particularly the motor rated current).
--------------
++ Omron VFD Fault code 1. Page >>
--------------------